Plan Review Notes For Permit 03020461 |
Permit Number |
03020461 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-20 00:00:00 | **************** UNSAT ************ | | | | 1)NOTE: SD NOT PERMITTED IN KITCHEN PER | | NFPA-72 8-1.4.1.2 | | | | 2)NOTE: SERVICE SHOWN AS 400A, PLEASE | | SIZE GROUNDING ELECTRODE CONDUCTORS PER | | 250-66 BASED ON SEC`S FROM 310-15. | | | | 3)NOTE: MAIN SHOWS A PANEL "B"? PLEASE | | PROVIDE PANEL SCHEDULE AND SHOW PANEL | | ON PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|