Plan Review Notes
Plan Review Notes For Permit 03020457
Permit Number 03020457
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-28 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.1.1.
  
 4) PLEASE REVISE #1 UNDER GENERAL NOTES
 ON C-1. THE CONSTRUCTION IS TYPE VI.
  
 5) INDICATE THE INTERNAL PRESSURE
 COEFFICENT ON C-1 WITH THE DESIGN
 CRITERIA. SEE FBC 1606.1.7.
  
 6) THE CONNECTION DETAIL 7 ON A-6 IS
 MISLABELED AS 1 ON A-6. PLEASE CORRECT.
  
 7) THE NOTE ON THE BOLLARD ON A-2 REFERS
 TO DETAIL #54. THIS DETAIL DOES NOT
 APPEAR TO BE ON THE PLANS.
  
 8) THE ENERGY CALCULATIONS INCORRECTLY
 LIST THE EXTERIOR WALLS AS WOOD FRAME.
  
 9) SPECIFY THAT THE DOOR BETWEEN THE
 GARAGE AND THE CONDITIONED SPACE IS A
 SOLID CORE OR INSULATED STEEL DOOR.
  
 10) INDICATE ON THE PLANS THAT THE WALL
 BETWEEN THE GARAGE AND THE CONDITIONED
 SPACE IS INSULATED.
  
 11) THE DETAILS ON SHEET A4 ARE LABELED
 INCORRECTLY.
  
 12) THERE ARE TWO DIFFERENT SHEETS OF
 DRAWINGS MARKED A4. PLEASE CORRECT.
  
 13) THE FRONT ELEVATION SHOWS TWO OVAL
 WINDOWS AT THE DEN AND THE FLOOR PLANS
 INDICATE SINGLE HUNG WINDOWS. PLEASE
 CORRECT.
  
 14) REVISE THE SLIDING GLASS DOOR DETAIL
 ON A4 TO INDICATE THAT THE ANCHORS ARE
 REQUIRED TO BE FASTENED THROUGH BUCKS
 LESS THAN 1-1/2" THICK AND INTO THE
 CONCRETE SUBSTRATE. SEE FBC 1707.4.4.2.
  
 14) THE INSTALLATION SCHEDULE AND KEY
 PLAN FOR THE STORM PANELS DOES NOT
 CORRESPOND WITH THE PLANS. PLEASE REVISE
  
 15) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE FRENCH DOOR
 - GLASS BLOCK (THE ONE SUBMITTED IS A
 PRELIMINARY NOA)
  
 16) PROVIDE THE MANUFACTURER'S SPECS.
 AND UL LISTING FOR THE ONE HOUR FIRE
 RATED GLASS BLOCK ASSEMBLY.
  
 18) THE OPENING SIZE INDICATED ON THE
 PLANS FOR THE GLASS BLOCK EXCEEDS THE
 MAXIMUM OPENING SIZE ALLOWED BY THE
 PRODUCT APPROVAL. PLEASE CORRECT.
  
 19) ONE OF THE PAGES OF THE DRAWINGS IS
 MISSING FROM THE PRODUCT APPROVAL FOR
 THE SINGLE HUNG WINDOWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202