Plan Review Notes For Permit 03020454 |
Permit Number |
03020454 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-11-04 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE NOTE THE FOLLOWING DISCREPANCIES | | ON THE PLANS,MAKE CORRECTIONS TO SAME | | AND RESUBMIT FOR REVIEW. | | | | THE 200 AMP PANEL SCHEDULE SHOWS | | CIRCUITS (3)-#12 ON 2-P0LE 20 AMP | | BREAKERS FEEDING THE POOL PANEL.THE | | RISER SHOWS # 6 WIRE ON A 20 AMP | | BREAKER FEEDING A 60 AMP PANEL.THE | | OTHER PANEL WITH THE POOL EQUIPMENT | | LISTED ON IT IS LISTED AS A 200 AMP | | PANEL. PLEASE CORRELATE | | FEEDS,SCHEDULES,PANELS AND OCP'S. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|