Plan Review Notes
Plan Review Notes For Permit 03020454
Permit Number 03020454
Review Stop E
Sequence Number 2
Notes
Date Text
2003-11-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING DISCREPANCIES
 ON THE PLANS,MAKE CORRECTIONS TO SAME
 AND RESUBMIT FOR REVIEW.
  
 THE 200 AMP PANEL SCHEDULE SHOWS
 CIRCUITS (3)-#12 ON 2-P0LE 20 AMP
 BREAKERS FEEDING THE POOL PANEL.THE
 RISER SHOWS # 6 WIRE ON A 20 AMP
 BREAKER FEEDING A 60 AMP PANEL.THE
 OTHER PANEL WITH THE POOL EQUIPMENT
 LISTED ON IT IS LISTED AS A 200 AMP
 PANEL. PLEASE CORRELATE
 FEEDS,SCHEDULES,PANELS AND OCP'S.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718