Plan Review Notes
Plan Review Notes For Permit 03020319
Permit Number 03020319
Review Stop B
Sequence Number 2
Notes
Date Text
2003-04-02 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ENERGY CALCULATIONS TO HAVE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORD
 2-PROVIDE SOIL TEST REPORT WITH ORIGINAL
 SIGNATURE AND SEAL. CHAPTER 471 FL.ST.
 3-STORM SHUTTERS: SEE ENGINEERED DWGS
 AND REVISE INSTALLATION SCHEDULE AS
 REQUIRED. CHECK DESIGN PRESSURES,
 PANEL MAX. SPAN, ANCHOR TYPE & SPACING
 AND MOUNTING CONDITIONS AND CONNECTION
 TYPE.
 4-SHEET A-4: SEE STAIR SECTION B/A-4 AND
 CLARIFY NOTES #1 AND #8. SEE SECTION
 1007.5.1 FBC 2001.