2003-02-24 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-FLOOD ZONE A8. WILL NEED TO PROVIDE |
| THE ELEVATION CERTIFICATE. |
| 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 3-SHEET A-4: REVISE STAIR KEY NOTE #1. |
| SEE SECTION 1007.5.1 FBC 2001 FOR |
| REQUIRED HANDRAIL HEIGHT. |
| **ALSO, REVISE HANDRAIL HEIGHT SHOWN ON |
| STAIR SECTION B/A-4. |
| 4-SHEET A-4: SPECIFY FIREBLOCKING |
| MATERIAL AND LOCATION. SEE SECTION |
| 2305.1.4 FBC 2001. |
| **NOTE: FIREBLOCKING AND DRAFSTOPPING |
| ARE NOT THE SAME THING. REVISE NOTE |
| #14 AS REQUIRED. |
| 5-PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| AT ALL CONCEALED SPACES. SEE SECTION |
| 2305.1.4 FBC 2001. |
| 6-SHEET A-5: SIZE OF VENT ON NOTE #14 |
| DOESN'T MATCH VENTILATION CALCULATIONS |
| REVISE AS REQUIRED. |
| 7-CLARIFY SIZE OF BUCKET SHOWN ON DETAIL |
| S6. SEE GIRDER TRUSS SIZE. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 8-DETAIL S21 DOESN'T MATCH CONDITIONS |
| SHOWN ON SECOND FLOOR FRAMING PLAN. |
| REVISE AS REQUIRED. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 9-SHOW NAILING ZONES IN ROOF FRAMING |
| PLAN. SEE SEC. 2306.1 CITY AMENDMENTS |
| TO FBC 2001. |
| 10-REVISE/UPDATE TRUSS ANCHOR SCHEDULE |
| TO MATCH USP PUBLISHED CATALOGUE. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 11-PROVIDE FIRECUT SPECIFICATIONS ON |
| STRUCTURAL WALL SECTIONS. SECTION |
| 2305.4 FBC 2001. |
| 12-DETAIL SECTION S2 HAS OVERLAPPING |
| INFORMATION. REVISE AS REQUIRED. |
| 13-DETAIL F14: SPECIFY HOW MUCH EMBED- |
| MENT FOR ANCHOR BOLTS. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 14-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| FRAMED OPENINGS TO RECEIVED ARCHED |
| WINDOWS. SEC. 104.2.1.2 CITY AMENDMENT |
| TO FBC 2001. |
| 15-PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS OR APPLY FOR A SEPARATE |
| PERMIT. |
| 16-SECOND FLOOR FRAMING PLAN IS MISSING |
| SOME CONNECTORS. EG. SPECIFY CONNECTOR |
| FOR GIRDER TRUSSES. SEE PLANS FOR |
| COMMENTS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |