Plan Review Notes For Permit 03020315 |
Permit Number |
03020315 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-27 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 2-FLOOD ZONE A8. NEED TO PROVIDE THE | | ELEVATION CERTIFICATE. | | 3-SHEET S-1: REVISE NOTE #24. SEE SEC. | | 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT. | | 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE | | THICKNESS IS LESS THAN 0.25". SECTION | | 2405.2.2 FBC 2001. | | 5-SHEET S-4: REVISE NOTE #1. SEE SECTION | | 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT. | | 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING | | AT ALL CONCEALED SPACES AS REQUIRED BY | | SEC. 2305.1.4 FBC 2001. | | 7-PROVIDE COMPLETE DETAIL/SECTION FOR | | TOP CONNECTION AT TOP OF COL. BETWEEN | | GARAGE AND KITCHEN. CLARIFY HOW ARE | | STRAPS HOLDING THE TOW GIRDER TRUSSES. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL | | WALL SECTIONS FOR FIRECUT REQUIREMENTS | | SEC. 2305.4 FBC 2001. | | 9-GARAGE DOOR STRUCTURAL BUCK DETAIL: | | SPECIFY EMBEDMENT FOR ANCHOR AND SIZE | | OF WASHER. SECTION 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. |
|