Plan Review Notes
Plan Review Notes For Permit 03020277
Permit Number 03020277
Review Stop B
Sequence Number 3
Notes
Date Text
2003-04-08 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE UPDATED SBBCI PRODUCT APPROVAL
 #2229A THAT MATCHES ENGINEERED DWGS.
 ALSO, REVISE DESIGN PRESSURES. SEE
 ENGINEERED DWGS FOR MAX./MIN. PANEL
 SPAN ALLOWED ACCORDING TO THE DESIGN
 PRESSURES. SEC. 104.2.1.2 CITY AMEND.
 MENTS TO FBC 2001.
 2-REVISE DETAIL S-21 FOR COLUMN LOCATED
 BETWEEN GARAGE AND STAIRWAY.
  
 **NOTE: THIS IS NOT A TRUSS TO TRUSS
 CONNECTION. CLARIFY HOW IS COLUMN
 SUPPORTING THE TWO GIRDER TRUSSES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 3-RE-SUBMIT ENERGY CALCULATIONS WITH
 ENGINEER'S ORIGINAL SIGNATURE AND SEAL
 AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES AND SEC. 103.0 CHAPTER 13 FBC
 2001.