Plan Review Notes For Permit 03020277 |
Permit Number |
03020277 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-04-08 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE UPDATED SBBCI PRODUCT APPROVAL | | #2229A THAT MATCHES ENGINEERED DWGS. | | ALSO, REVISE DESIGN PRESSURES. SEE | | ENGINEERED DWGS FOR MAX./MIN. PANEL | | SPAN ALLOWED ACCORDING TO THE DESIGN | | PRESSURES. SEC. 104.2.1.2 CITY AMEND. | | MENTS TO FBC 2001. | | 2-REVISE DETAIL S-21 FOR COLUMN LOCATED | | BETWEEN GARAGE AND STAIRWAY. | | | | **NOTE: THIS IS NOT A TRUSS TO TRUSS | | CONNECTION. CLARIFY HOW IS COLUMN | | SUPPORTING THE TWO GIRDER TRUSSES. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | | 3-RE-SUBMIT ENERGY CALCULATIONS WITH | | ENGINEER'S ORIGINAL SIGNATURE AND SEAL | | AS REQUIRED BY CHAPTER 471 FLORIDA | | STATUTES AND SEC. 103.0 CHAPTER 13 FBC | | 2001. |
|