Plan Review Notes For Permit 03020277 |
Permit Number |
03020277 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-28 00:00:00 | BUILDING CHECKLIST: | | 1-IMPACT FEES RECEIPT NUMBER DOESN'T | | MATCH NUMBER ON STAMPED DRAWINGS. | | PROVIDE MATCHING RECEIPT. | | 2-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS OR APPLY FOR SEPARATE PERMIT. | | 3-DETAIL S21 DOESN'T APPLY TO COLUMN | | LOCATED BETWEEN GARAGE AND STAIRWAY. | | PROVIDE COMPLETE DETAIL SHOPWING HOW | | ARE STRAPS HOLDING THE TWO GIRDER | | TRUSSES AT THIS LOCATION. SECTION | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | 4-REVISE CONNECTOR TC-1 SPECIFIED ON | | ROOF FRAMING PLAN @ WOOD FRAMED WALL. | | NEED WOOD TO WOOD CONNECTOR. SECTION | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | 5-34SH WINDOW DON'T PROVIDE 24" CLEAR | | OPENING IN HEIGHT REQUIRED BY SECTION | | 1005.4.4 FBC 2001. REVISE/CLARIFY AS | | REQUIRED. |
|