2003-05-13 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM, A
 NEW LARGER SERVICE IS NOW BEING SHOW
 W/WIRE NOT RATED FOR FOR SERVICE SIZE,
 PLEASE SIZE CONDUCTORS PER 310-15,240-3
  
 2)NOTE:PLEASE CLARIFY GROUNDING ELECTR-
 ODE COMING FROM CONDUIT.??
 PLEASE SHOW GROUNDING ELECTRODE FOR
 BLDG AS / FOOTER STEEL, COLD WATER ETC
 PER 250-50/250-31
  
 3)NOTE: PLEASE CLARFIY SIZE OF EXISTING
 SEC`S AND METER. SHOW EXISTING MAIN OCP.
  
 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 12 CIR PANEL AND 150 PANEL SCHEDULE
 SHOWS ATLEAST 28?
  
 5)NOTE: PLAN SHOWS METER AT SAME BLDG,
 AND YET NO OTHER (EXIST) MAIN/DISC IS
 SHOWN?? 230-72/215-5 ETC
  
 PLEASE NOTE, ALL PLANS MUST BE
 SIGNED DATED AND SEALED BY THE ARCH/ENG
 OF RECORD. PER FS/FAC 471.025/481.221
 61G15-23.002/61G1-16.004,,,
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE QUESTIONS, PLEASE
 CALL.
  