2003-05-13 00:00:00 | ************* UNSAT ************** | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM, A | | NEW LARGER SERVICE IS NOW BEING SHOW | | W/WIRE NOT RATED FOR FOR SERVICE SIZE, | | PLEASE SIZE CONDUCTORS PER 310-15,240-3 | | | | 2)NOTE:PLEASE CLARIFY GROUNDING ELECTR- | | ODE COMING FROM CONDUIT.?? | | PLEASE SHOW GROUNDING ELECTRODE FOR | | BLDG AS / FOOTER STEEL, COLD WATER ETC | | PER 250-50/250-31 | | | | 3)NOTE: PLEASE CLARFIY SIZE OF EXISTING | | SEC`S AND METER. SHOW EXISTING MAIN OCP. | | | | 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS | | 12 CIR PANEL AND 150 PANEL SCHEDULE | | SHOWS ATLEAST 28? | | | | 5)NOTE: PLAN SHOWS METER AT SAME BLDG, | | AND YET NO OTHER (EXIST) MAIN/DISC IS | | SHOWN?? 230-72/215-5 ETC | | | | PLEASE NOTE, ALL PLANS MUST BE | | SIGNED DATED AND SEALED BY THE ARCH/ENG | | OF RECORD. PER FS/FAC 471.025/481.221 | | 61G15-23.002/61G1-16.004,,, | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE QUESTIONS, PLEASE | | CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|