2003-02-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-AMEND 98 DESIGN MANUAL
  
 1) DUE TO THE NATURE OF THE JOB, ALL
 WORK SHALL BE CONSIDERED NEW CONSTRUCT-
 ION. FHA-98 WILL BE ENFORCED AT THIS
 TIME FOR UNITS #1, 2 & 3. PER DESIGN
 MANUAL, REQUIREMENTS 1 THRU 7 SHALL BE
 SHOWN ON PLANS. SPECIFICATION "A" OR "B"
 WILL BE SHOWN FOR ALL BATHROOMS. ALL
 CLEAR FLOOR SPACE WILL BE SUPERIMPOSED
 ON PLANS FOR BATHROOMS AND KITCHEN.
 BACKING LOCATIONS, LENGTH & HEIGHT RE-
 QUIREMENTS DETAIL SHALL BE SUBMITTED.
 2) SHTS P-2 & P-3 FLOOR PLAN AND SANT.
 RISER DIAGRAM, PER SECTION 909.1 WET
 VENT-ONLY THE FIXTURES WITHIN THE BATH-
 ROOM GROUP SHALL CONNEDT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.
 3) A WATER RISER DIAGRAM IS REQUIRED.
 SHOW ALL WATER HAMMER ARRESTORS REQUIRED
 BY 604.9, (WASH MACHINE, DISHWASHER, &
 ICE MAKER), AND LOCATED AS REFERENCED BY
 THIRD NOT ON SHEET P-2.
 4) SHT P-3 NOTE #12, AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE FROM REFER-
 ENCE.
  