Plan Review Notes For Permit 03012371 |
Permit Number |
03012371 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-07 00:00:00 | DENIED: | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | AREA BEING VENTILATED) OR TABLE 403.3 | | FOR MECHANICAL VENTILATION. | | | | PLAN SHEET M-1 FIRST FLOOR MECH PLAN | | DOES NOT CORRELATE WITH THE A-2 GROUND | | FLOOR PLAN. | | | | MECHANICAL PLANS INDICATE DRYER EXHAUST | | AND TOILET EXHAUST SHARING THE SAME | | 8" X 8" SHAFT.PLEASE CLARIFY (SEE | | 2001 FBC(M) 504.1). | | | | PLAN SHEET M-3 HVAC GENERAL NOTES, | | "PROVIDE MAIN & AUXILIARY CONDENSATE | | DRAINS FOR ALL A/C UNITS & DRAIN TO | | EXTERIOR PERMEABLE GROUND OR AS SHOWN | | ON PLAN" SECONDARY DRAIN MUST TERMINATE | | AT A "CONSPICUOUS POINT" THE "EXTERIOR" | | IS NOT CONSPICUOUS. | | | | PLANS INDICATE AHU CLOSET IS BEING USED | | AS A PLENUM.NO COMBUSTIBLES ALLOWED | | IN PLENUM (PVC).2001 FBC(M) 602.2.1. | | | | AS PER THE FAIR HOUSING ACT, HVAC | | CONTROLS SHALL BE A MINIMUM OF 15" AFF | | & 48" MAXIMUM AFF. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|