2003-02-07 00:00:00DENIED:
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 PLAN SHEET M-1 FIRST FLOOR MECH PLAN
 DOES NOT CORRELATE WITH THE A-2 GROUND
 FLOOR PLAN.
  
 MECHANICAL PLANS INDICATE DRYER EXHAUST
 AND TOILET EXHAUST SHARING THE SAME
 8" X 8" SHAFT.PLEASE CLARIFY (SEE
 2001 FBC(M) 504.1).
  
 PLAN SHEET M-3 HVAC GENERAL NOTES,
 "PROVIDE MAIN & AUXILIARY CONDENSATE
 DRAINS FOR ALL A/C UNITS & DRAIN TO
 EXTERIOR PERMEABLE GROUND OR AS SHOWN
 ON PLAN" SECONDARY DRAIN MUST TERMINATE
 AT A "CONSPICUOUS POINT" THE "EXTERIOR"
 IS NOT CONSPICUOUS.
  
 PLANS INDICATE AHU CLOSET IS BEING USED
 AS A PLENUM.NO COMBUSTIBLES ALLOWED
 IN PLENUM (PVC).2001 FBC(M) 602.2.1.
  
 AS PER THE FAIR HOUSING ACT, HVAC
 CONTROLS SHALL BE A MINIMUM OF 15" AFF
 & 48" MAXIMUM AFF.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.