2003-02-14 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) CONSTRUCTION IS TYPE VI UNPROTECTED. |
| PLEASE CORRECT COVER SHEET. |
| |
| 3) PROVIDE A CURRENT SIGNED AND SEALED |
| SURVEY. |
| |
| 4) FBC 2304.1.2 REQUIRES THE SOIL TO BE |
| TREATED FOR TERMITES. PLEASE INDICATE ON |
| PLANS. |
| |
| 5) SPECIFY THE DEPTH/THICKNESS OF THE |
| EXTERIOR FOOTING. |
| |
| 6) INDICATE LOCATIONS AND MATERIALS FOR |
| THE DRAFTSTOPPING IN THE ATTIC REQUIRED |
| BY FBC 2305.2.3. |
| |
| 7) INDICATE FIREBLOCKING ON SECTIONS AND |
| DETAILS AT CONCEALED SPACES AND WHERE |
| REQUIRED BY FBC 705.3 AND 2305.1. |
| INCLUDING THE STAIRS, FIREPLACE AND |
| CHIMNEYS. |
| |
| 8) INDICATE DRAFTSTOPPING LOCATIONS IN |
| THE FLOOR/CEILING ASSEMBLIES AS REQUIRED |
| BY FBC 2305.2.2. |
| |
| 9) INDICATE ADEQUATE ATTIC VENTILATION |
| AS REQUIRED BY FBC 2309.7. |
| |
| 10) THE ONE HOUR RATED WALLS PROVIDING |
| TENANT SEPARATION ARE REQUIRED TO BE |
| CONTINOUS TO THE EXTERIOR OF THE |
| EXISTING WALLS. |
| |
| 11)THE ONE HOUR SEPARATION AT THE FLOOR/ |
| CEILING ASSEMBLY IS REQUIRED TO EXTEND |
| TO THE EXTERIOR OF THE EXISTING WALLS. |
| |
| 12) FIREPLACE/CHIMNEY IS NOT INDICATED |
| ON THE FLOOR PLAN. INDICATE IF IT IS TO |
| BE FUNCTIONING OR ABANDONDED. |
| |
| 13) ONE MEANS OF EGRESS IS REQUIRED |
| FROM EACH APARTMENT BY FBC 1004.1.2. |
| THE MINIMUM CLEAR OPENING OF THE EXIT |
| DOOR IS REQUIRED TO BE 32 INCHES PER |
| FBC 1012 AND TABLE 1004. THE EXIT DOORS |
| AT THE ONE HOUR FIRE RATED ENCLOSED |
| STAIRS FROM THE UPSTAIRS APTS. WILL |
| HAVE TO BE INCREASED TO 3 FT. DOORS. |
| THE BUILDING OFFICIAL HAS AGREED TO |
| ALLOW THE DOORS TO SWING INTO THE STAIR |
| ENCLOSURE RATHER THAN OPEN OR PROJECT |
| UPON PUBLIC PROPERTY (SEE FBC 3203). THE |
| OTHER OPTION IS TO HAVE EXTERIOR EXITWAY |
| STAIRS, BUT THIS WILL BE MUCH MORE |
| INVOLVED THAN THE OTHER SENARIO. ONE |
| HOUR SEPARATION FROM THE INTERIOR OF THE |
| BUILDING, ONE HOUR RATED WALL TO |
| SEPARATE FROM ADJACENT PROPERTY, ETC. |
| SEE FBC 1006.2 THROUGH 1006.2.6. |
| |
| 14) THE EXTERIOR DOORS ON THE SOUTH |
| ELEVATION THAT OPEN INTO THE PUBLIC WAY |
| ARE REQUIRED TO BE CHANGED TO SWING IN. |
| SEE FBC 3203. |
| |
| 15) INDICATE THE POSITIVE AND NEGATIVE |
| WINDLOADS FOR ALL EXTERIOR DOOR AND |
| WINDOW OPENINGS. |
| |
| 16) PROVIDE A WINDOW IN THE SECOND STORY |
| MASTER BEDROOM THAT COMPLIES WITH FBC |
| 1005.4 FOR EMERGENCY ESCAPE AND RESCUE |
| OPENINGS. |
| |
| 17) SPECIFY ON THE PLANS THE GUARDRAIL |
| HEIGHT, SPACING OF INTERMEDIATE RAILS, |
| BOTTOM RAIL, ETC. FOR THE EXTERIOR |
| BALCONY AND STAIRS. SEE FBC 1015. |
| |
| 18) INDICATE THE FOUNDATION FOR THE |
| EXTERIOR STAIRS, BALCONY AND ROOF. |
| |
| 19) THE INTERIOR STAIRS DO NOT COMPLY |
| WITH FBC 1007.3. THE SUM OF TWO RISERS |
| AND A TREAD (EXCLUSIVE OF NOSING) SHALL |
| BE BETWEEN 24 AND 25 INCHES. PLEASE |
| REVISE. |
| |
| 20) SPECIFY FIREBLOCKING AT ENCLOSED |
| SPACES OF STAIRS AS REQUIRED BY FBC |
| 2305.1.4(3). |
| |
| 21) THE BUCK DETAILS ON A-10 DO NOT |
| CONCUR WITH THE REST OF THE PLANS WHICH |
| INDICATE A METAL FRAME WALL INSIDE THE |
| EXISTING WOOD FRAME AND STUCCO FACADE. |
| PLEASE REVISE. SPECIFY THE SPACING OF |
| THE FASTENERS USED TO ATTACH THE BUCKS |
| TO THE STRUCTURE. |
| |
| 22) PLEASE CLARIFY IF THE BRACING |
| BETWEEN THE NEW WALL AND THE FACADE IS |
| TO BE LOCATED HORIZONTALLY AT EACH STUD |
| 16"O.C. AND HOW WILL THEY BE LOCATED AT |
| DOOR AND WINDOW OPENINGS. |
| |
| 23) SPECIFY THE FASTENERS AND CONNECTORS |
| THAT WILL BE USED TO ATTACH AND SUPPORT |
| THE 2X FLOOR JOISTS. PROVIDE DETAILS. |
| |
| 24) INDICATE LOCATIONS AND PROVIDE |
| CONSTRUCTION DETAILS FOR SHEAR WALLS. |
| |
| 25)SPECIFY THE CONNECTIONS AND FASTENERS |
| AT INTERIOR AND EXTERIOR BEARING WALLS. |
| INDICATE THE CONNECTORS THAT WILL BE |
| USED TO RESIST UPLIFT AND GRAVITY LOADS. |
| |
| 26) THE AREA OF WALL OPENINGS IN THE |
| FIRST FLOOR OF THE NORTH WALL EXCEEDS |
| THE PERCENT OF OPENINGS ALLOWED BY TABLE |
| 600 OF THE FBC. THE AREA OF WALL IS |
| TAKEN FROM FLOOR TO CEILING OF EACH |
| FLOOR. THE PERCENT OF WALL AREA ALLOWED |
| AS OPENINGS IS 20% FOR A WALL OVER 3 FT. |
| TO 10 FT. FROM THE PROPERTY LINE. PLEASE |
| COORDINATE WITH HISTORIC PRESERVATION |
| DEPARTMENT. |
| |
| 27) THE ENERGY CALCULATIONS ARE REQUIRED |
| TO BE SIGNED AND DATED BY THE OWNER/ |
| AGENT. THE R-VALUES LISTED FOR THE |
| EXTERIOR WALLS ARE INCORRECT. THE |
| EXTERIOR WALLS ARE FRAME NOT CONCRETE. |
| PLEASE CORRECT. |
| |
| 28) PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. MISSLE |
| IMPACT PROTECTION IS REQUIRED BY FBC |
| 1606.1.4. |
| |
| 29) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - EXTERIOR DOORS |
| - SINGLE HUNG WINDOWS (A PRELIMINARY NOA |
| WAS SUBMITTED) |
| - ALL NEW EXTERIOR DOORS AND WINDOWS |
| |
| 30) BECAUSE THE STRUCTURE WAS BUILT AND |
| OCCUPIED PRIOR TO MARCH 13, 1991, IT |
| DOES NOT HAVE TO COMPLY WITH THE FEDERAL |
| FAIR HOUSING ACT, UNLESS THE INTERIOR OF |
| THE BUILDING INCLUDING ALL STRUCTURAL |
| PORTIONS OF FLOORS AND CEILINGS IS |
| REMOVED, AND A NEW BUILDING IS |
| CONSTRUCTED BEHIND THE OLD FACADE. |
| PLEASE INDICATE ON THE PLANS THE |
| PORTIONS OF THE EXISTING STRUCTURE THAT |
| ARE TO REMAIN. THE BUILDING OFFICIAL HAS |
| REQUESTED THAT BACKING FOR GRAB BARS BE |
| INSTALLED AT THE TOILETS AND BATHTUBS. |
| PLEASE SHOW THIS ON PLANS. |
| |
| 31) THE VALUE OF THE WORK FOR THIS |
| PROJECT IS LISTED AS $52,000.00 ON THE |
| PERMIT APPLICATION. THIS AMOUNT IS MUCH |
| TOO LOW. THE COST TO CONSTRUCT AN R-2 |
| APARTMENT BUILDING OF TYPE VI |
| UNPROTECTED CONSTRUCTION USING THE VALUE |
| FROM SBCCI FOR AVERAGECONSTRUCTION |
| WITH THE FLORIDA MULTIPLIER OF 1.04 IS |
| $48.88 PER SQUARE FT. THE PLANS LIST THE |
| SQUARE FOOTAGE AS 4640. THE TOTAL COST |
| IS $226,803.20. YOUR COST WILL BE MINUS |
| THE COST OF THE EXTERIOR FINISH AND THE |
| ANY OTHER ITEMS THAT ARE EXISTING. |
| PLEASE REVISE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |