Plan Review Notes For Permit 03012209 |
Permit Number |
03012209 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-10 00:00:00 | PROVISO: | | | | PLANS DO NOT INDICATE RATED WALLS, | | FLOORS OR PARTITIONS.PLEASE INDICATE | | ALL FIRE DAMPERS WHETHER NEW OR EXISTING | | ON PLAN. | | | | FIRE DAMPERS SHALL BE INSTALLED IN | | ACCORDANCE WITH MANUFACTURER'S | | INSTALLATION INSTRUCTIONS IN THE | | FOLLOWING LOCATIONS. | | 1. DUCTS PENETRATING WALLS OR PARTITIONS | | HAVING FIRE RESISTANCE RATING OF 1 OR | | MORE HRS. | | 2. DUCTS PENETRATING SHAFT WALLS HAVING | | A FIRE RESISTANCE RATING OF 1 OR MORE | | HRS. | | 3. DUCTS PENETRATING ONLY ONE FLOOR OF A | | BUILDING REQUIRING THE PROTECTION OF | | VERTICAL OPENING (FIRE DAMPER). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|