Plan Review Notes For Permit 03012191
Permit Number 03012191
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-25 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SOIL REPORT FROM UNIVERSAL
 REQUIRES A 16 INCH WIDE MONOLITHIC
 FOUNDATION. THE PLANS INDICATE THE
 MONOLITHIC FOUNDATION AT 12 INCHES WIDE.
 PLEASE CORRECT.
  
 3) THE STRUCTURE IS LOCATED IN AN AO
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202