2003-02-11 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) PLEASE CLARIFY NOTE #9 UNDER GENERAL |
| NOTES ON SHEET 1 TO INCLUDE WINDOWS THAT |
| ARE WITHIN THREE FEET HORIZONTALLY OF |
| THE TUB OR SHOWER. SEE FBC 2405.2.1. |
| |
| 3) SPECIFY ON THE PLANS THAT THE WIRE |
| MESH IN THE SLAB IS REQUIRED TO BE |
| SUPPORTED AT A MAXIMUM OF THREE FEET ON |
| CENTER PER FBC 1909.3. |
| |
| 4) SPECIFY THE SIZES OF THE FIXED GLASS |
| TRANSOM AND THE SIDELITE AT THE FRONT |
| DOOR ON THE PLANS. |
| |
| 5) THE ROOF FRAMING PLAN ON 3A, 3B AND |
| 3C SPECIFY AN A-5 TRUSS CONNECTOR FOR |
| THE HIP GIRDER AT THE GARAGE. THERE IS |
| NO A-5 CONNECTOR LISTED IN THE ANCHOR |
| SCHEDULE ON SHEET 2. PLEASE CLARIFY. |
| |
| 6) PLEASE SPECIFY THE LENGTH OR EMBED |
| DEPTH OF THE 5/8" EXPANSION BOLTS FOR |
| THE OVERHEAD GARAGE DOOR BUCKS ON DETAIL |
| 3 ON SHEET 4. |
| |
| 7) THE ENERGY CALCULATION FORM INDICATES |
| THAT THE HVAC CREDIT FOR CEILING FANS IS |
| BEING TAKEN. PLEASE INDICATE THE MINIMUM |
| FAN SIZE REQUIRED FOR EACH ROOM ON THE |
| PLANS. SEE FBC CHAPTER 13-607.1.A.1 AND |
| TABLE 6-6. |
| |
| 8) PROVIDE THE MANUFACTURER'S SPECS. AND |
| UL LISTING INFORMATION FOR THE ONE HOUR |
| RATED GLASS BLOCK ASSEMBLY. |
| |
| 9) THE NORANDEX SITE SPECIFIC PRODUCT |
| APPROVALS ARE REQUIRED TO BE SEALED BY |
| THE DESIGNER OF RECORD OF THE STRUCTURE |
| AND THE LOCATION OF THE JOB IS ALSO |
| REQUIRED ON THE FORM. NOTE:THE SIGNATURE |
| ON THE PRODUCT APPROVAL SUBMITTED IS |
| FROM THE ENGINEER (STEVE WALSH), WHO HAS |
| NOT SIGNED AND SEALED THE PLANS FOR THIS |
| PROJECT. |
| |
| 10) PROVIDE A PRODUCT APPROVAL FOR THE |
| 96"X 60" GLIDER WINDOW WITH AN XOX |
| CONFIGURATION AS SHOWN ON THE PLANS. THE |
| NORANDEX PRODUCT APPROVALS SUBMITTED DO |
| NOT COVER THIS SIZE OR CONFIGURATION. |
| |
| 11) THE SURVEY HAS THE INCORRECT LOMR |
| CASE NUMBER AND DATE FOR THE FLOOD ZONE. |
| |