Plan Review Notes For Permit 03012111 |
Permit Number |
03012111 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-03-06 00:00:00 | DENIED | | | | 1) THE SITE SPECIFIC PRODUCT APPROVALS | | FOR THE NORANDEX PRODUCTS ARE REQUIRED | | BY THE BUILDING OFFICIAL TO HAVE THE | | EMBOSSED SEAL OF THE DESIGNER OF RECORD | | FOR THE STRUCTURE AND THE LOCATION OF | | THE JOB ON THE FORM. | | | | 2) THE R VALUES LISTED ON THE ENERGY | | CALCULATIONS FOR THE EXTERIOR AND | | ADJACENT WALLS ARE REVERSED. PLEASE | | CORRECT. | | | | 3) THE OPENING SIZES ON THE STORM PANEL | | SCHEDULE ARE INCORRECT FOR OPENINGS 4 | | AND 10. | | | | 4) THERE ARE NO PRODUCT APPROVALS FOR | | THE STORM PANELS IN THE PACKAGE. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)659-8096 EXT.8202 |
|