Plan Review Notes For Permit 03011977 |
Permit Number |
03011977 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-05 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SHT A-1 SEPARATE TOILET FACILITIES | | ARE REQUIRED PER SECTION 403.2 | | 2) SHT A-1 WATER COOLER SHALL COMPLY | | WITH ARI-1010 PER SECTION 410.1. MANUF. | | INFORMATION REQUIRED AT FINAL. | | 3) SHT A-1 EMERGENCY EYE WASH/SHOWER, | | MANUF. INFORMATION REQUIRED FOR REVIEW. | | 4) SHT P1 PLUMBING SPECIFICATIONS #7, | | AIR CHAMBERS NOT APPROVED. PLEASE DELETE | | FROM REFERENCE. | | 5) SHT P1 WATER RISER, AIR CHAMBERS ARE | | NOT APPROVED. IF WATER HAMMER ARRESTORS | | ARE USED, (SEC 604.9), THEY SHALL BE | | LOCATED NEAR THE FIXTURE IN AN "EFFECT- | | IVE RANGE" NOT AT THE TOP OF THE DROP IN | | THE CEILING. | | 6) SHT P1 SANITARY RISER & FLAT PLAN, | | ONLY THE FIXTURES WITHIN THE BATHROOM | | GROUP SHALL CONNECT TO THE WET-VENTED | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF | | THE WET VENT. SECTION 909.1 - THE JANIT- | | OR SINK SHOULD HAVE ITS OUN VENT LINE | | AND TIE IN DOWNSTREAM OF THE BATHROOM | | GROUP. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|