Plan Review Notes
Plan Review Notes For Permit 03011977
Permit Number 03011977
Review Stop P
Sequence Number 1
Notes
Date Text
2003-02-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 SEPARATE TOILET FACILITIES
 ARE REQUIRED PER SECTION 403.2
 2) SHT A-1 WATER COOLER SHALL COMPLY
 WITH ARI-1010 PER SECTION 410.1. MANUF.
 INFORMATION REQUIRED AT FINAL.
 3) SHT A-1 EMERGENCY EYE WASH/SHOWER,
 MANUF. INFORMATION REQUIRED FOR REVIEW.
 4) SHT P1 PLUMBING SPECIFICATIONS #7,
 AIR CHAMBERS NOT APPROVED. PLEASE DELETE
 FROM REFERENCE.
 5) SHT P1 WATER RISER, AIR CHAMBERS ARE
 NOT APPROVED. IF WATER HAMMER ARRESTORS
 ARE USED, (SEC 604.9), THEY SHALL BE
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" NOT AT THE TOP OF THE DROP IN
 THE CEILING.
 6) SHT P1 SANITARY RISER & FLAT PLAN,
 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. SECTION 909.1 - THE JANIT-
 OR SINK SHOULD HAVE ITS OUN VENT LINE
 AND TIE IN DOWNSTREAM OF THE BATHROOM
 GROUP.
  
 REVIEW BY KEN STEVENS