2003-02-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH 250-66,AND THE SYSTEM
 WITH 250-50,ENTIRE ARTICLE.
  
 2} THE SMALL APPLIANCE CIRCUITS ARE
 SHOWN AS 1200 VA.PLEASE CALCULATE PER
 220-16(A).
  
 3} PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 4} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 6} PLEASE LOCATE SMOKE DETECTORS TO
 COMPLY WITH NFPA-72 8-1.4.1.6,ENTIRE
 ARTICLE.
  
 7} ALL RECEPTACLE SPACING TO COMPLY WITH
 210-52.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392