Plan Review Notes For Permit 03011955 |
Permit Number |
03011955 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-25 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE NECESSARY CHANGES TO | | PLANS AND RESUBMIT FOR REVIEW. | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | MUST COMPLY WITH 250-66,AND THE SYSTEM | | WITH 250-50,ENTIRE ARTICLE. | | | | 2} THE SMALL APPLIANCE CIRCUITS ARE | | SHOWN AS 1200 VA.PLEASE CALCULATE PER | | 220-16(A). | | | | 3} PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI | | PROTECT--ED PER 210-8-A-6. | | INCLUDES KITCHEN ISLANDS. | | | | 4} PLEASE LIST THE REQ`D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | CIRCUIT PROTECTION. PER 210-12 | | | | 5} PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG. | | | | 6} PLEASE LOCATE SMOKE DETECTORS TO | | COMPLY WITH NFPA-72 8-1.4.1.6,ENTIRE | | ARTICLE. | | | | 7} ALL RECEPTACLE SPACING TO COMPLY WITH | | 210-52. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|