Plan Review Notes
Plan Review Notes For Permit 03011955
Permit Number 03011955
Review Stop B
Sequence Number 1
Notes
Date Text
2003-03-06 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SHEET A-13 IS MISSING FROM THE PLANS.
  
 4) THE DESIGN CRITERIA ON A-5 IS NOT
 CORRECT. PLEASE REVISE TO 2001 FBC,
 ASCE 7-98 AND 140 MPH WIND SPEED.
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) REVISE ROOF FASTENING INFORMATION ON
 A5 TO COMPLY WITH CITY OF WPB AMENDMENTS
 TABLE 2306.1. ZONE 3 SPACING 4"OC AT
 EDGES AND 6"OC INTERMEDIATE. 8D RING
 SHANK NAILS REQUIRED IN ZONE 3 FOR MEAN
 ROOF HEIGHT GREATER THAN 25'.
  
 6) INDICATE ATTIC ACCESS TO SPACE ABOVE
 GUEST ROOM. SEE FBC 2309.6.
  
 7) SEPARATE PERMITS ARE REQUIRED FOR THE
 CONCRETE WALL AND POOL.
  
 8) PROVIDE WINDOW AND DOOR SCHEDULE.
  
 9) EGRESS WINDOWS OR DOORS REQUIRED FOR
 SLEEPING ROOMS. FBC 1005.4
  
 10) THE FULL BATH ON THE GROUND FLOOR IS
 REQUIRED TO HAVE DOORS WITH 29" CLEAR
 OPENING.FBC CHAPTER 11.
  
 11) WINDOWS WITHIN 3' HORIZONTALLY OF
 TUB OR SHOWER SHALL BE SAFETY GLAZING.
 FBC 2405.2 IMPACT GLASS IS ACCEPTABLE.
  
 12) PROVIDE AN ENGINEERED ANALYSIS OF
 THE REINFORCED CONCRETE BLOCK WALL
 SUPPORTING BEAM B-3.
  
 13) SPECIFY THE LOCATIONS AND MATERIAL
 THAT WILL BE USED TO PROVIDE THE
 DRAFTSTOPPING AT THE FLOOR/CEILING
 ASSEMBLY. SEE FBC 2305.2.2.
  
 14) SPECIFY ATTIC VENTILATION REQUIRED
 BY FBC 2309.7.
  
 15) PROVIDE A DETAIL OF THE INTERIOR
 LOAD BEARING WALLS.
  
 16) PROVIDE BUCK DETAILS FOR THE DOORS,
 WINDOWS AND GARAGE DOORS.
  
 17) THE FIRST FLOOR PLAN ON A1 INDICATES
 A 42" PREFAB FIREPLACE AND THE SECTION
 ON A12 IS A MASONRY FIREPLACE. PLEASE
 CLARIFY.
  
 18) INDICATE ON PLANS THAT CHIMNEY IS TO
 EXTEND AT LEAST 2' HIGHER THAN ANY
 PORTION OF ROOF WITHIN 10' HORIZONTALLY.
 SEE FBC 2804.2.4.
  
 19) THE FOOTING INDICATED IN THE SECTION
 ON A12 DOES NOT CORRESPOND WITH THE
 FOUNDATION PLAN ON A2.
  
 20) PROVIDE ADDITIONAL DETAILS FOR THE
 MASONRY CHIMNEY AND FIREPLACE. INCLUDE
 THE FLUE SIZE AND THICKNESS, THE FIRE-
 PLACE DIMENSIONS, FIREBOX LINING, FRESH
 AIR INTAKE, HEARTH EXTENSION DIMENSIONS,
 FIREPLACE OPENING SIZE, ETC. SEE FBC
 2113 AND 2114.
  
 21) FLUE DAMPER IS REQUIRED BY FBC 13-
 606.1.1(3).
  
 22) PROVIDE UL LISTING INFORMATION FOR
 SPARK ARRESTOR.
  
 23) IF PREFAB FIREPLACE PROVIDE
 MANUFACTURER'S SPECIFICATIONS AND
 LISTING INFORMATION.
  
 24) INDICATE FIREBLOCKING AT CONCEALDED
 SPACES OF THE STAIRS AT THE TOP AND
 BOTTOM OF THE RUNS. FBC 2305.1.4(3)
  
 25) GUARDRAILS ON THE OPEN SIDES OF
 STAIRS ARE REQUIRED TO BE 36" HIGH AND
 INTERMEDIATE RAILS SHALL REJECT THE
 PASSAGE OF A 4" SPHERE. SEE FBC 1015 AND
 1026.5
  
 26) SPECIFY THE BALCONY RAILINGS HEIGHT,
 INTERMEDIATE RAIL SPACING, BOTTOM RAIL
 HEIGHT, FASTENING DETAILS, ETC. PROVIDE
 CONSTRUCTION DETAILS FOR COLUMNS TO
 WHICH RAILS ARE ATTACHED. FBC 1015 AND
 1608.2.2
  
 27) PROVIDE A PRECAST LINTEL SCHEDULE.
  
 28) UPDATE THE CONCRETE STANDARDS IN
 NOTES ON A5 TO ACI-99. FBC CHAPTER 35
  
 29) PROVIDE PRODUCT APPROVALS FOR THE
 DOUBLE INSWING FRONT DOORS.
  
 30) THE TRUSS LAYOUT AND TRUSS DRAWINGS
 ARE REQUIRED TO BE SIGNED SEALED AND
 DATED BY THE TRUSS ENGINEER AND BE
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD. THE DESIGNER OF RECORD SHOULD
 STAMP AND SIGN THE LAYOUT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202