Plan Review Notes For Permit 03011816 |
Permit Number |
03011816 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-19 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 2-FLOOD ZONE A8: NEED TO PROVIDE THE | | ELEVATION CERTIFICATE. | | 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED | | BETWEEN GARAGE AND STAIRWAY. CLARIFY | | HOW ARE ATRAPS HOLDING THE TWO GIRDER | | TRUSSES. SEC. 104.2.1.2 CITY AMENDMENT | | TO FBC 2001. | | 4-34SH WINDOW DON'T PROVIDE THE 24" MIN. | | CLEAR HEIGHT REQUIRED BY SEC. 1005.4.4 | | FBC 2001. ARE THEY CUSTOM MADE WINDOWS | | CLARIFY/REVISE AS REQUIRED. | | 5-PROVIDE SOIL TEST REPORT PRIOR TO | | CONSTRUCTION. |
|