2003-02-05 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 W/ PANEL SCHEDULE. PLEASE SEE PANEL "A'"
 SHOWS 2P40A OCP ON #10 AWG FOR 60A SUB-
 -PANEL.?
 PLEASE ALSO SHOW LOCATION OF SUB-PANEL
 ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372