Plan Review Notes For Permit 03011798 |
Permit Number |
03011798 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | 1) FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON | | WATER SERVICE. (ADD TO NOTES) | | 2) FBC-2001 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 3) ALL CHANGES TO A SIGNED AND SEALED | | SET OF PLANS SHALL BE INITIALED AND | | DATED BY THE ENGINEER OF RECORD OR NEW | | SHEETS SUBMITTED IN SET OF PLANS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|