Plan Review Notes For Permit 03011787 |
Permit Number |
03011787 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-10 00:00:00 | *********** UNSAT ************ | | | | 1)NOTE: PLEASE CORRELATE OCP/AWG WITH | | RISER DIAGRAM. PANEL SHOWS #10 AND 40A | | FOR 60A SUB PANEL. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|