Plan Review Notes For Permit 03011787 |
Permit Number |
03011787 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-18 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 2-FLOOD ZONE A8: NEED TO PROVIDE THE | | ELEVATION CERTIFICATE. | | 3-CLARIFY DETAIL S21. HOW ARE TRUSSES | | SUPPORTED BY STRAPS ON COLUMN BETWEEN | | GARAGE AND STAIRWAY. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | 4-REVISE CONNECTOR TC-1 SPECIFIED ON | | ROOF FRAMING PLAN AT FRONT WALL. NEED | | WOOD TO WOOD CONNECTOR. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | 5-34SH WINDOW DOESN'T PROVIDE THE 24" | | CLEAR HEIGHT. SEC. 1005.4.4 FBC 2001. | | CLARIFY/REVISE AS REQUIRED. | | 6-PROVIDE SOIL TEST REPORT PRIOR TO | | CONSTRUCTION. |
|