Plan Review Notes For Permit 03011785 |
Permit Number |
03011785 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-21 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 2-FLOOD ZONE A8. NEED TO PROVIDE THE | | ELEVATION CERTIFICATE. | | 3-CLAIFY/REVISE HEIGHT OF HANDRAIL AND | | GUARDRAIL. SEE SEC. 1007.5.1 FBC 2001, | | NOTE #24 ON SHEET A-1 AND NOTE #1 AND | | STAIR SECTION ON SHEET A-4. REVISE AS | | REQUIRED. | | 4-PROVIDE SOIL TEST REPORT PRIOR TO | | CONSTRUCTION. |
|