2003-01-25 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) L/P TANK SHALL BE SECURED. PLEASE
 PROVIDE DETAIL. TANK SHALL BE INSPECTED
 PRIOR TO COVERING.
 2 FOLLOWING INFORMATION REQUIRED FOR
 GAS PERMIT APPLICATION.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. FOR DRYER-CEILING
 HEIGHT NOT SHOWN ON PLANS.
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377