Plan Review Notes For Permit 03011776 |
Permit Number |
03011776 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-01-25 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1) L/P TANK SHALL BE SECURED. PLEASE | | PROVIDE DETAIL. TANK SHALL BE INSPECTED | | PRIOR TO COVERING. | | 2 FOLLOWING INFORMATION REQUIRED FOR | | GAS PERMIT APPLICATION. | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. | | B. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | THRU 402.5.2 AND TABLES 402(1) THRU | | 402(34). | | C. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES (A)(3). | | D. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | GAS CODE SECTION 304. FOR DRYER-CEILING | | HEIGHT NOT SHOWN ON PLANS. | | E. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|