Plan Review Notes For Permit 03011742 |
Permit Number |
03011742 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-05-24 00:00:00 | AS PER OUR CONVERSATION - 8" B VENT IS | | FOR "HEAT REMOVAL" FROM THE BAKERY OVEN, | | REVISION APPLICATION INDICATES THIS IS | | AN 8" "FLUE VENT".PLEASE CLARIFY - | | HEAT HOOD & FLUE VENT ARE TWO DIFFERENT | | ANIMALS.8" FLUE INDICATES GAS AND HAS | | DIFFERENT REQUIREMENTS THAN DUCT FOR | | A HEAT HOOD. | | | | PLANS ORIGINALLY SUBMITTED ARE STAMPED | | BY ENGINEER, I WAS NOT INFORMED OF THIS | | DURING OUR CONVERSATION. |
|