Plan Review Notes
Plan Review Notes For Permit 03011742
Permit Number 03011742
Review Stop P
Sequence Number 1
Notes
Date Text
2003-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) GREASE TRAP SHALL BE SIZED BY RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE (561)
 837-4074 PER WASTE ORD. #2938-96
 2) SHT P-1 ALL SINKS IN A FOOD PREP AREA
 SHALL DRAIN INDIRECTLY INTO A FLOOR SINK
 EXCEPT HAND SINKS.
 3) SHTS P-1/P-2 WHAT WILL THE FLOOR
 TROUGH BE USED TO DRAIN? ALL INDIRECT
 WASTE (CONDENSATE) SHALL DRAIN TO A F.S.
 4) SHT P-2 WATER RISER, A WATER HAMMER
 ARRESTOR IS REQUIRED AT THE ICE MACHINE.
 SEC 604.9
 5) SHT P-2 GREASE RISER, JANITOR SINK
 NOT SHOWN ON RISER.
 6) SHT P-2 WATER HEATER DETAIL, FLOOR
 SINK IS REQUIRED FOR PAN DRAIN AND P/T
 DISCHARGE.
 7) FOLLOWING INFORMATION REQUIRED FOR
 SEPARATE GAS PERMIT APPLICATION.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 8) SHT P-2 DRINKING FOUNTAIN SHALL
 COMPLY WITH 11-4.15 AND ALL SUBSECTIONS.
 ALSO SEE 11-4.1.3.(10)(A) PROVISIONS
 SHALL BE MADE FOR THOSE WHO HAVE DIFFI-
 CULTY BENDING OR STOOPING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377