2003-03-17 00:00:0000) AIR CHAMBERS ARE NOT APPROVED. WATER
 HAMMER ARRESTORS SHALL BE REQUIRED FOR
 QUICK CLOSING VALVES. IF INSTALLED THEY
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT AT THE TOP OF THE
 DROP.