2003-05-08 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO
 THE PLANS FOR CODE COMPLIANCE,AND
 RESUBMIT FOR REVIEW.
  
 1} NOTE THE #2 FEEDER SHOWN IS ONLY
 RATED FOR 125 AMPS.PLEASE CHECK THE
 SIZE AT THE SERVICE AND IF THE CORRECT
 SIZE IS #2 THE MAIN BREAKER MUST BE
 CHANGED TO 125 AMPS,OR THE SERVICE MUST
 BE UPGRADED TO 200 AMPS WITH 2/0 WIRE.
  
 2} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ'D PER 210-52E
  
 3} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.ALSO SHALL BE GFI
 PROTECTED PER 210-8(A)(6),LIST SAME ON
 PLANS.
  
 4} THE RECEPTACLE SPACING IN THE
 FAMILY,OFFICE AND MASTER BEDROOMS MUST
 COMPLY WITH 210-52. SEE REDLINED PLANS.
  
 5} THERE MUST BE A RECEPTACLE IN THE
 MASTER BATH TO COMPLY WITH 210-52(D).
  
 6} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S), PER 210-11-C-3
 MUST BE 20A AND #12AWG,ON PANEL
 SCHEDULE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  