Plan Review Notes
Plan Review Notes For Permit 03011301
Permit Number 03011301
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-07 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED THE ELEVATION
 CERTIFICATE.
 3-SHEET A-1: REVISE NOTE #24. SEE SEC.
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE NOTE #1. SEE SECTION
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION AT TOP OF COLUMN BETWEEN
 GARAGE AND KITCHEN. CLARIFY HOW IS
 COLUMN TOP CONNECTOR HOLDING THE TWO
 GIRDER TRUSSES COMING FROM DIFFERENT
 DIRECTIONS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALLS FOR FIRECUT REQUIREMENTS SEC.
 2305.4 FBC 2001.
 9-DETAIL R19: SPECIFY ALL CONNECTORS.
 ROOF FRAMING PLAN DOESN'T SPEC THEM.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.