2003-02-07 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS UNDER A SEPARATE PERMIT. |
| 2-FLOOD ZONE A8. NEED THE ELEVATION |
| CERTIFICATE. |
| 3-SHEET A-1: REVISE NOTE #24. SEE SEC. |
| 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT. |
| 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE |
| THICKNESS IS LESS THAN 0.25". SECTION |
| 2405.2.2 FBC 2001. |
| 5-SHEET A-4: REVISE NOTE #1. SEE SECTION |
| 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT. |
| 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| AT ALL CONCEALED SPACES AS REQUIRED BY |
| SEC. 2305.1.4 FBC 2001. |
| 7-PROVIDE COMPLETE DETAIL/SECTION FOR |
| CONNECTION AT TOP OF COLUMN BETWEEN |
| GARAGE AND KITCHEN. CLARIFY HOW IS |
| COLUMN TOP CONNECTOR HOLDING THE TWO |
| GIRDER TRUSSES COMING FROM DIFFERENT |
| DIRECTIONS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL |
| WALLS FOR FIRECUT REQUIREMENTS SEC. |
| 2305.4 FBC 2001. |
| 9-DETAIL R19: SPECIFY ALL CONNECTORS. |
| ROOF FRAMING PLAN DOESN'T SPEC THEM. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER |
| FOR GARAGE DOOR STRUCTURAL BUCK DETAIL |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |