Plan Review Notes
Plan Review Notes For Permit 03011285
Permit Number 03011285
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-13 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-SHEET A-1: REVISE NOTE #24. SEE SEC.
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE NOTE #1. SEE SECTION
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION AT TOP OF COLUMN LOCATED
 BETWEEN GARAGE AND KITCHEN AND SHOWING
 HOW ARE THE TWO TRUSSES SUPPORTED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-DETAIL R19: SPECIFY ALL CONNECTORS.
 ROOF FRAMING PLAN DOESN'T SPECIFY THEM
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-GARAGE DOOR STRUCTURAL BUCK DETAIL:
 SPECIFY HOW MUCH EMBEDMENT FOR ANCHOR
 AND WASHER SIZE. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 11-PROVIDE SOIL TEST REPORT PRIOR TO
 CONSTRUCTION.