2003-07-15 00:00:00 | BUILDING DENIED |
| |
| 1) THE ENERGY CALCULATION FORMS ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE |
| OWNER/AGENT. |
| |
| 2) SUBMIT SIGNED AND SEALED COPIES OF |
| THE TEST REPORT FOR THE 90 DEGREE |
| SLIDING GLASS DOORS. |
| |
| 3) THE ENGINEERING FOR THE BAY WINDOW |
| MULLION REFERENCES THE WRONG LOT NUMBER. |
| SITE SPECIFIC ENGINEERING IS REQUIRED TO |
| BE REVIEWED AND APPROVED BY THE DESIGNER |
| OF RECORD FOR THE STRUCTURE. THE NOTES |
| ON THE DRAWING INDICATE THAT THE MULLION |
| IS NOT CAPABLE OF SUPPORTING THE DEAD |
| LOADS OF THE WINDOWS ABOVE AND THE |
| PRODUCT APPROVAL FOR THE STORE FRONT |
| WINDOW WALL DOES NOT ADDRESS SUPPORTING |
| ANY DEAD LOAD FROM ABOVE. THERE ARE NO |
| OVERALL DIMENSIONS FOR THE MULLION GIVEN |
| |
| 4) THE PRODUCT APPROVAL THAT SUBMITTED |
| DOES NOT INDICATE THAT THE WINDOW WALL |
| SYSTEM CAN BE INSTALLED ON A RADIUS. |
| SITE SPECIFIC ENGINEERING WITH DRAWINGS |
| AND ANALYSIS,WHICH HAS BEEN REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD, IS |
| REQUIRED. TESTING OF THE ASSEMBLY IS |
| REQUIRED FOR IMPACT RESISTANCE. THE |
| ASSEMBLY AS INDICATED ON THE PLANS IS |
| THE UPPER AND LOWER WINDOW WALL SYSTEMS |
| AND THE MULLION BETWEEN THEM. IF THE |
| ASSEMBLY IS NOT TESTED, THEN IT MUST BE |
| SHUTTERED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |