Plan Review Notes
Plan Review Notes For Permit 03011211
Permit Number 03011211
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-28 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 DRAWINGS AND RESUBMIT FOR REVIEW.
  
 1} THE PANEL IN THE GARAGE IS NOT SHOWN
 ON THE RISER DIAGRAM.
  
 2} THERE IS NO PANEL SCHEDULE FOR THE
 PANEL IN THE GARAGE.PLEASE PROVIDE
 SAME.( NOTES 1&2 REFER TO GARAGE #2).
  
 3} THE WATER HEATER IS NOT IN THE LOAD
 CALC OR LISTED ON A PANEL SCHEDULE,IF
 IT IS TO BE GAS PLEASE INDICATE SAME.
  
 4} ALL DISCONNECT LOCATIONS MUST COMPLY
 WITH 110-26,CANNOT BE LOCATED BEHIND THE
 UNITS.
  
 5} THE CONDENSER LOCATIONS ON THE
 ELECTRICAL DRAWINGS DO NOT MATCH THE
 MECHANICAL PLANS.PLEASE CORRELATE.ALSO
 THE AHU DESIGNATIONS.
  
 6} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 7} BEDROOM #5 IS NOT LISTED ON THE
 PANELSCHEDULE.(NOTE BOTH PANELS ARE
 FULL!!)
  
 8} PLEASE CHECK RECEPTACLE SPACING PER
 210-52,ENTIRE ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392