Plan Review Notes For Permit 03011211 |
Permit Number |
03011211 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-28 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE NECESSARY CHANGES TO | | DRAWINGS AND RESUBMIT FOR REVIEW. | | | | 1} THE PANEL IN THE GARAGE IS NOT SHOWN | | ON THE RISER DIAGRAM. | | | | 2} THERE IS NO PANEL SCHEDULE FOR THE | | PANEL IN THE GARAGE.PLEASE PROVIDE | | SAME.( NOTES 1&2 REFER TO GARAGE #2). | | | | 3} THE WATER HEATER IS NOT IN THE LOAD | | CALC OR LISTED ON A PANEL SCHEDULE,IF | | IT IS TO BE GAS PLEASE INDICATE SAME. | | | | 4} ALL DISCONNECT LOCATIONS MUST COMPLY | | WITH 110-26,CANNOT BE LOCATED BEHIND THE | | UNITS. | | | | 5} THE CONDENSER LOCATIONS ON THE | | ELECTRICAL DRAWINGS DO NOT MATCH THE | | MECHANICAL PLANS.PLEASE CORRELATE.ALSO | | THE AHU DESIGNATIONS. | | | | 6} PLEASE NOTE FRONT AND REAR | | RECEPTS REQ`D PER 210-52E | | | | 7} BEDROOM #5 IS NOT LISTED ON THE | | PANELSCHEDULE.(NOTE BOTH PANELS ARE | | FULL!!) | | | | 8} PLEASE CHECK RECEPTACLE SPACING PER | | 210-52,ENTIRE ARTICLE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|