2003-03-20 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) FBC 2305.2.2 REQUIRES DRAFTSTOPPING |
| PARALLEL TO THE MAIN FRAMING MEMBERS IN |
| FLOOR/CEILING ASSEMBLIES SEPARATING IT |
| INTO AREAS NO GREATER THAN 550 SQFT. |
| INDICATE THE LOCATIONS AND MATERIAL THAT |
| WILL BE USED ON THE PLANS. |
| |
| 3) SPECIFY THE GUARDRAIL HEIGHT, SPACING |
| OF INTERMEDIATE RAILS, BOTTOM RAIL |
| SPACING, ATTACMENT METHOD FOR THE |
| EXTERIOR BALCONY AND THE INTERIOR LOFTS. |
| |
| 4) PROVIDE DETAILS OF STAIRS. SPECIFY |
| THE TREAD AND RISER DIMENSIONS PER FBC |
| 1007.3. CIRCULAR STAIRS SHALL COMPLY |
| WITH FBC 1007.8.3. SPIRAL STAIRWAY SHALL |
| COMPLY WITH FBC 1007.8.2. PROVIDE DETAIL |
| OF GUARDRAILS ON THE OPEN SIDE OF THE |
| STAIRS. SEE FBC 1015 & 1026.5. |
| |
| 5) INDICATE FIREBLOCKING AT VERTICAL AND |
| HORIZONTAL COCEALED DRAFT OPENINGS AND |
| CONCEALED SPACES OF STAIR STRINGERS AT |
| THE TOP AND BOTTOM OF THE RUN. SEE FBC |
| 2305.1 & 2305.1.4. |
| |
| 6) INDICATE THE LOCATIONS OF THE SHEAR |
| WALLS AT THE SECOND FLOOR WOOD FRAME |
| WALLS ON THE PLANS. PROVIDE DETAILS AND |
| LOCATIONS OF HOLD DOWNS. |
| |
| 7) NO ID TAGS ARE GIVEN ON THE PLANS |
| THAT CORRESPOND TO THE COLUMN DETAILS ON |
| 5F. PROVIDE ID TAGS FOR ALL OF THE |
| COLUMNS AND BEARING POINTS ON THE |
| FOUNDATION PLAN ON SHEET 4 AND PROVIDE |
| DETAILS FOR EACH. |
| |
| 8) THE CROSS SECTION ON 5F REFERS TO |
| DETAIL 7 ON 5C FOR THE STEEL COLUMN. |
| THERE IS NO DETAIL ON 5C. |
| |
| 9) THE SECTION ON 4S1 HAS INCORRECT |
| DIMENSION FOR THE FOOTING. |
| |
| 10) PROVIDE A SQFT BREAKDOWN OF HOUSE. |
| INDICATE THE SQFT LIVING AREA ON EACH |
| FLOOR, PORCHES, GARAGES, ETC. |
| |
| 11) THE ENERGY CALCULATIONS LIST THE |
| CONDITONED FLOOR AREA AS 6950 SQFT. IS |
| THIS THE TOTAL SQFT OF THE HOUSE OR THE |
| CONDITIONED SPACE? |
| |
| 12) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - SLIDING GLASS DOOR |
| - THE PRODUCT APPROVAL FOR THE ROOF |
| TILE HAS EXPIRED (12-16-02). |
| - PROVIDE COVER SHEET FOR THE DESIGNER |
| SERIES-FIXED WINDOWS NOA # 02-0318.02 |
| THAT IS IN WITH THE STORMLINE DOORS. |
| - THE TEST INFO SUBMITTED FOR THE |
| WINDOOR 90 DEGREE SLIDING GLASS DOOR IS |
| NOT AN ACCEPTABLE PRODUCT APPROVAL. IT |
| MUST BE METRO-DADE, SBCCI OR SITE |
| SPECIFIC ENGINEERING.(ENGINEERED |
| DRAWINGS SHOWING ALL ATTACHMENTS ARE |
| REQUIRED) |
| |
| 13) THE PRODUCT APPROVAL FOR THE STORE- |
| FRONT WINDOW IS LIMITED TO A MAXIMUM |
| FRAME HEIGHT OF TWELVE FT. A STRUCTURAL |
| HORIZONTAL MULLION THAT IS ON A RADIUS |
| WILL BE REQUIRED. THE PRODUCT APPROVAL |
| DOES NOT COVER A RADIUS APPLICATION SUCH |
| AS THIS ASSEMBLY. SITE SPECIFIC |
| ENGINEERING ALONG WITH A ENGINEERED |
| ANALYSIS AND DRAWINGS WILL BE REQUIRED. |
| |
| 14) THE HEADER DETAIL ON 4S3 FOR THE 90 |
| DEGREE SLIDING GLASS DOORS AT THE SECOND |
| FLOOR SHOWS THE C9X15 CHANNEL ANCHORED |
| TO THE WALL WITH EXPANSION BOLTS. THE |
| SECOND FLOOR WALLS IN THIS LOCATION IS |
| WOOD FRAME. SEE 5A & 5E. THE TRUSSES IN |
| THE DETAIL ARE INDICATED WITH ID TAGS |
| THAT DO NOT CORRESPOND WITH TRUSS IDS ON |
| 5E. |
| |