2003-02-07 00:00:00 | 1) SITE PLAN SHALL SHOW ALL FIRE |
| HYDRANTS LOCATED IN THE IMMEDIATE |
| VICINTY OF THE BUILDING. |
| |
| 2) PLEASE CLEARLY ILLUSTRATE TENANT |
| SEPARTION WALLS ON FLOOR PLANS. |
| |
| 3) PLEASE INDICATE FIRE EXTINGUISHER |
| LOCATIONS. |
| |
| 4) BUILDING ADDRESS REQUIRED. |
| |
| 5) APARTMENT DOORS SHALL BE AT LEAST |
| 20 MINUTE FIRE RATED. |
| |
| 6) IT WAS NOTED THAT A STOVE IS PRESENT |
| IN THE CLUBHOUSE. IF NO HOOD,DUCT,OR |
| FIRE SUPPRESSION SYSTEM IS PLANNED, |
| ONLY BOILING OF WATER WILL BE ALLOWED. |
| NO COOKING THAT PRODUCES SMOKE OR |
| GREASE LADEN VAPORS WILL BE ALLOWED |
| WITHOUT THE PROPER FIRE SAFETY |
| EQUIPMENT. |
| |
| 7) IF NO FIRE SPRINKLERS ARE PLANNED, |
| THEN ALL STORAGE ROOMS MUST BE AT |
| LEAST ONE HOUR FIRE SEPARATED WITH |
| 45 MINUTE OPENING PROTECTIVES. |
| |
| 8) ANOTHER EXIT SIGN IS REQUIRED NEAR |
| FIRST FLOOR STORAGE NEAR THE GAME ROOM |
| TO DIRECT PERSONS. |
| |
| 9) STAIR TREADS AND RISERS ARE NOT |
| PROPER. |
| |
| 10) BATHROOM DOORS WHEN OPENED INTERFERE |
| WITH THE PROPER WIDTH OF THE CORRIDOR. |
| |
| 11) PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATION INFORMATION FOR WALLS |
| AND CEILINGS. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 659-8096,EXT.8497 |
| 835-2910 |