Plan Review Notes
Plan Review Notes For Permit 03011199
Permit Number 03011199
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-13 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 PLEASE SUBMIT PANEL SCHEDULES.
 INFORMATION ON PANELS ETC
 2)NOTE: PLEASE SIZE SEC`S PER 310-15/
 310-16, 240-3.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EEQUIPMENT.
  
 PLEASE COMPLETE PLANS FOR REVIEW,PLEASE
 NOTE THERE MAY BE ADDTIONAL COMMENTS DUE
 TO CIRCUITING,PANELS,LOADS ETC
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER NEC 220, MIXED USE, 220-3,220-10,
 220-11,220-13,215-3,23-42 ETC.
  
 5)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372