Plan Review Notes
Plan Review Notes For Permit 03011199
Permit Number 03011199
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-20 00:00:00THE HC RAMP AND LANDING ON SHOWN ON THE
 SOUTH SIDE, SHEET A1 AND THE FLAT AREA
 ON THE NORTH SIDE DO NOT COMPLY WITH
 FBC 11-4.8.4 AND 11-4.13.6.PLEASE
 REVISE AS NECESSARY.
  
 SHOW THE FINISH FLOOR ELEVATION
 REALTIVE TO THE SURROUNDING TOPOGRAPHY.
 FBC 104.2
  
 SHEET A2.THE DOORS SHOWN SWINGING INTO
 THE CORRIDOR FROM THE TOILET ROOMS DO
 NOT COMPLY WITH FBC 1012.1.4.
  
 SHEET A2 THE AREA SHOWN AS CLUBHOUSE IS
 AN ASSEMBLY OCCUPANCY USE.THE DOORS
 MUST SWING IN THE DIRECTION OF TRAVEL,
 BE SIDE SWINGING AND PROVIDE 32" CLEAR
 WIDTH. SEE FBC 1012.1.2
  
 PLEASE PROVIDE THE ROOF COVERING
 INFORMATION IN ACCORDANCE WITH FBC
 104.2.1.1.
  
 SHEET A4 THE STAIR SECTION MAKES DESIGN
 REFERENCES AS "PER CODE" WHICH IS NOT
 ANACCEPTABEL SUBSTITUTE FOR SPECIFIC
 DESIGN INFORMATION.SEE FBC 1007.5 AND
 1015.
  
 THE STAIRS DO NOT COMPLY WITH THE RISER
 AND TREAD REQUIREMENTS OF FBC 1007.3.1.
  
 THE "STAIRWAYS" DO NOT MEET THE 1/2
 DIAGONAL DISTANCE REQUIREMENT OF FBC
 1006.2.2.
  
 SHEET A7.SHOW A CONNECTION DETAIL FOR
 THE 3-2X12 BEAM TO THE MASONRY COLUMNS
 SHOWN ON THE NORTH MOST SIDE.
  
 SHOW A FRAMING AND FASTENING DETAIL FOR
 THE SUSPENDED GYP BOARD CEILING SHOWN ON
 SHEET A8. FBC 104.2.
  
 SHOW THE DESIGN LOADS FOR THE BALCONIES
 AND THE STAIRS, AND THE COMPONENT AND
 CLADDING PRESSURES FOR THE ROOF.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY THE PERMIT PLANS STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
 THE $237,600.00 DECLARED PERMIT
 VALUATION IS TOO LOW FOR THIS SCOPE OF
 WORK.THE CITY VALUATION IS
 $410792.00, PLEASE PAY AN ADDITIONAL
 $961.22 PERMIT FEES TO THE CITY.