2003-02-20 00:00:00 | THE HC RAMP AND LANDING ON SHOWN ON THE |
| SOUTH SIDE, SHEET A1 AND THE FLAT AREA |
| ON THE NORTH SIDE DO NOT COMPLY WITH |
| FBC 11-4.8.4 AND 11-4.13.6.PLEASE |
| REVISE AS NECESSARY. |
| |
| SHOW THE FINISH FLOOR ELEVATION |
| REALTIVE TO THE SURROUNDING TOPOGRAPHY. |
| FBC 104.2 |
| |
| SHEET A2.THE DOORS SHOWN SWINGING INTO |
| THE CORRIDOR FROM THE TOILET ROOMS DO |
| NOT COMPLY WITH FBC 1012.1.4. |
| |
| SHEET A2 THE AREA SHOWN AS CLUBHOUSE IS |
| AN ASSEMBLY OCCUPANCY USE.THE DOORS |
| MUST SWING IN THE DIRECTION OF TRAVEL, |
| BE SIDE SWINGING AND PROVIDE 32" CLEAR |
| WIDTH. SEE FBC 1012.1.2 |
| |
| PLEASE PROVIDE THE ROOF COVERING |
| INFORMATION IN ACCORDANCE WITH FBC |
| 104.2.1.1. |
| |
| SHEET A4 THE STAIR SECTION MAKES DESIGN |
| REFERENCES AS "PER CODE" WHICH IS NOT |
| ANACCEPTABEL SUBSTITUTE FOR SPECIFIC |
| DESIGN INFORMATION.SEE FBC 1007.5 AND |
| 1015. |
| |
| THE STAIRS DO NOT COMPLY WITH THE RISER |
| AND TREAD REQUIREMENTS OF FBC 1007.3.1. |
| |
| THE "STAIRWAYS" DO NOT MEET THE 1/2 |
| DIAGONAL DISTANCE REQUIREMENT OF FBC |
| 1006.2.2. |
| |
| SHEET A7.SHOW A CONNECTION DETAIL FOR |
| THE 3-2X12 BEAM TO THE MASONRY COLUMNS |
| SHOWN ON THE NORTH MOST SIDE. |
| |
| SHOW A FRAMING AND FASTENING DETAIL FOR |
| THE SUSPENDED GYP BOARD CEILING SHOWN ON |
| SHEET A8. FBC 104.2. |
| |
| SHOW THE DESIGN LOADS FOR THE BALCONIES |
| AND THE STAIRS, AND THE COMPONENT AND |
| CLADDING PRESSURES FOR THE ROOF. |
| |
| BEFORE A PERMIT TO CONSTRUCT MAY BE |
| ISSUED IMPACT FEES MUST BE PAID TO THE |
| COUNTY THE PERMIT PLANS STAMPED BY THAT |
| OFFICE AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| CALL 561-233-5025 FOR MORE INFORMATION. |
| |
| THE $237,600.00 DECLARED PERMIT |
| VALUATION IS TOO LOW FOR THIS SCOPE OF |
| WORK.THE CITY VALUATION IS |
| $410792.00, PLEASE PAY AN ADDITIONAL |
| $961.22 PERMIT FEES TO THE CITY. |