2003-03-26 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03011198 |
| ADD: 539 CLEMATIS ST |
| CONT: COMPLETE PROPERTY MANAGEMENT |
| TEL: (561)626-2778 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1707.4.3 EACH EXTERIOR DOOR |
| ASSEMBLY NOT COVERED BY 1707.4.2 |
| (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| ED FOR A PERIOD EQUAL TO THE QUANITY |
| 3600/ V WHERE THE TIME PERIOD IS IN |
| SECTIONS AND V IS IN MILES PER HR TAKEN |
| FROM FIGURE 1606. THE TIME PERIOD SHALL |
| ALSO INCLUDE A 10 SECOND PERIOD AT A |
| LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| PRESSURE. DADE COUNTY & SBCCI REPORTS |
| ARE ACCEPTED. |
| |
| MISSING PRODUCT TESTING REPORT FOR DOOR |
| # 3 THE EXTERIOR VESTIBULE DOOR. |
| |
| 2)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)659-8096 X 8412 |
| FAX: (561)659-8026 |