Plan Review Notes For Permit 03011198 |
Permit Number |
03011198 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-04 00:00:00 | PROVISO:MECHANICAL PERMIT 03020138 | | | | 1.PLAN SHEET A1.00 REFLECTED CEILING | | PLAN, PLEASE NOTE CLEARANCES AROUND AHU | | SHALL BE SUFFICIENT TO ALLOW FOR REPAIR, | | SERVICE, REPLACEMENT OR INSPECTION. | | 2001 FBC(M) 306.1. | | | | 2.PLAN SHEET M1.00, RETURN AIR FROM | | THE RETAIL SPACE (101) INTO THE | | VESTIBULE (102) SHALL BE DUCTED. | | | | 3.PLAN SHEET M1.00 A/C SCHEDULE NOTE | | #6, FIRESTAT IN RETURN AIR DUCT...2001 | | FBC(M) 606.2.1, DETECTORS SHALL BE | | INSTALLED IN THE SUPPLY AIR DUCT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|