2003-02-04 00:00:00PROVISO:MECHANICAL PERMIT 03020138
  
 1.PLAN SHEET A1.00 REFLECTED CEILING
 PLAN, PLEASE NOTE CLEARANCES AROUND AHU
 SHALL BE SUFFICIENT TO ALLOW FOR REPAIR,
 SERVICE, REPLACEMENT OR INSPECTION.
 2001 FBC(M) 306.1.
  
 2.PLAN SHEET M1.00, RETURN AIR FROM
 THE RETAIL SPACE (101) INTO THE
 VESTIBULE (102) SHALL BE DUCTED.
  
 3.PLAN SHEET M1.00 A/C SCHEDULE NOTE
 #6, FIRESTAT IN RETURN AIR DUCT...2001
 FBC(M) 606.2.1, DETECTORS SHALL BE
 INSTALLED IN THE SUPPLY AIR DUCT.
  