Plan Review Notes
Plan Review Notes For Permit 03011090
Permit Number 03011090
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-06 00:00:00BUILDING REVIEW CHECKLIST:
 1-AREA CALCULATIONS ARE INCORRECT.
 REVISE PLANS AS REQUIRED.
 2-REVISE ENERGY CALCULATIONS AS REQUIRED
 TO MATCH CORRECTED FLOOR PLANS.
 3-REVISE IMPACT FEE A/C AREA TO MATCH
 CORRECTED PLANS.
 4-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS OR APPLY FOR SEPARATE PERMIT.
 5-PROVIDE COMPLETE SPECIFICATIONS FOR
 GARAGE DOOR STRUCTURAL BUCK DETAIL.
 SPECIFY ANCHOR EMBEDMENT AND WASHER
 SIZE. SEC. 104.2.1.2 CITY AMENDMENTS.
 6-BUILDING SECTION A/A-5: REVISE HEIGHT
 OF HANDRAIL. SEE SEC. 1007.5.1 FBC
 2001. **NOTE: HANDRAIL AND GUARDRAIL
 ARE NOT THE SAME.
 7-NEED RECORDED NOTICE OF COMMENCEMENT.