Plan Review Notes For Permit 03011084 |
Permit Number |
03011084 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-03-27 00:00:00 | BUILDING REVIEW SECOND CHECKLIST: | | 1-AREA CALCULATIONS ARE INCORRECT. | | ARCHITECT TO REVISE SHEET C-1 AND A-1. | | 2-ENERGY CALCULATIONS TO HAVE ENGINEER'S | | ORIGINAL SIGNATURE AND SEAL AS REQ'D | | BY CHAPTER 471 FLORIDA STATUTES AND | | SEC. 103.0 CHAPTER 13 FBC 2001. | | 3-REVISE STORM SHUTTERS INSTALLATION | | SCHEDULE TO MATCH INFORMATION GIVEN ON | | THE ENGINEERED DRAWINGS. CHECK THE | | DESIGN PRESSURES AND THE MAXIMUM PANEL | | SPAN ALLOWED. ALSO, CHECK FOR ANCHOR | | SPACING ACCORDING TO DESIGN PRESSURES, | | EDGE DISTANCE, CONNECTION TYPE AND | | PANEL SPAN SHOWN ON ENGINEERED DWGS. | | **ALSO, CLARIFY WHY SOMETIMESSHUTTERS | | PRODUCT APPROVALS ARE SUBMITTED AS | | SITE SPECIFIC AND SOMETIMES PRODUCT | | APPROVAL ARE SUBMITTED WITH THE SBCCI | | PRODUCT APPROVAL REPORT. |
|