2003-03-27 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1-AREA CALCULATIONS ARE INCORRECT.
 ARCHITECT TO REVISE SHEET C-1 AND A-1.
 2-ENERGY CALCULATIONS TO HAVE ENGINEER'S
 ORIGINAL SIGNATURE AND SEAL AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES AND
 SEC. 103.0 CHAPTER 13 FBC 2001.
 3-REVISE STORM SHUTTERS INSTALLATION
 SCHEDULE TO MATCH INFORMATION GIVEN ON
 THE ENGINEERED DRAWINGS. CHECK THE
 DESIGN PRESSURES AND THE MAXIMUM PANEL
 SPAN ALLOWED. ALSO, CHECK FOR ANCHOR
 SPACING ACCORDING TO DESIGN PRESSURES,
 EDGE DISTANCE, CONNECTION TYPE AND
 PANEL SPAN SHOWN ON ENGINEERED DWGS.
 **ALSO, CLARIFY WHY SOMETIMESSHUTTERS
 PRODUCT APPROVALS ARE SUBMITTED AS
 SITE SPECIFIC AND SOMETIMES PRODUCT
 APPROVAL ARE SUBMITTED WITH THE SBCCI
 PRODUCT APPROVAL REPORT.