2003-02-06 00:00:00BUILDING REVIEW CHECKLIST:
 1-AREA CALCULATIONS ARE INCORRECT.REVISE
 AS REQUIRED.
 2-REVISE ENERGY CALCULATIONS AS REQUIRED
 TO MATCH CORRECT AREAS IN FLOOR PLANS.
 3-REVISE AREA CALCULATIONS ON IMPACT
 FEES STAMP TO MATCH CORRECTED PLANS.
 4-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS OR APPLY FOR SEPARATE PERMIT.
 5-PROVIDE COMPLETE SPECIFICATIONS FOR
 GARAGE STRUCTURAL BUCK DETAIL. NEED
 ANCHOR EMBEDMENT AND WASHER SIZE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-BUILDING SECTION A/A-5: REVISE HEIGHT
 OF HANDRAIL. SEE SECTION 1007.5.1 FBC
 2001. ****NOTE: HANDRAIL AND GUARDRAIL
 ARE NOT THE SAME.
 7-NEED RECORDED NOTICE OF COMMENCEMENT.