Plan Review Notes For Permit 03011078 |
Permit Number |
03011078 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-12 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE INFORMATION ON DETAIL | | 41/S1. MISSING ANCHOR SIZE AND WASHER. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | 2-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS UNDER A SEPARATE PERMIT. | | 3-REVISE EXTERIOR RIGHT ELEVATION. NOTE | | #4 DOESN'T APPLY BECAUSE TIE BEAM ELE- | | VATION WAS RAISED TO AVOID HAVING ONE | | HR FIRE RATED ASSEMBLY AT TRUSS END AS | | REQUIRED BY TABLE 600 FBC 2001. | | 4-PROVIDE COMPLETE DETAIL CONNECTION AT | | TOP OF COLUMN P2 SHOWN ON 2ND FLOOR | | FRAMING PLAN. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. |
|