Plan Review Notes For Permit 03011049 |
Permit Number |
03011049 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-02-21 00:00:00 | BUILDING PROVISO | | | | 1) PROVIDE CORRECTED ENERGY CALCULATION | | FORMS. THE R-VALUES FOR THE EXTERIOR | | WALLS AND ADJACENT WALLS ARE REVERSED ON | | THE FORMS. | | | | 2) SUBMIT THE MANUFACTURER'S | | SPECIFICATIONS AND UL LISTING | | INFORMATION FOR THE ONE HOUR FIRE RATED | | GLASS BLOCK ASSEMBLY AT THE ZERO LOT | | LINE PRIOR TO INSTALLATION. | | | | 3) SUBMIT A CORRECTED STORM PANEL | | INSTALLATION SCHEDULE PRIOR TO | | INSTALLATION. |
|