Plan Review Notes
Plan Review Notes For Permit 03011049
Permit Number 03011049
Review Stop B
Sequence Number 1
Notes
Date Text
2003-02-06 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY ON THE PLANS THAT THE WIRE
 MESH IN THE SLAB WILL BE SUPPORTED AS
 REQUIRED BY FBC 1909.3.
  
 3) THE WINDOW IN BATH #2 WHICH IS WITHIN
 THREE FT. HORIZONTALLY OF THE TUB/SHOWER
 IS REQUIRED TO HAVE SAFETY GLASS. THIS
 IS NOT CLEARLY INDICATED BY GENERAL NOTE
 #9 ON SHEET 1. PLEASE CLARIFY. SEE
 FBC 2405.2.1.
  
 4) SPECIFY THE SIZE OF THE ATTIC ACCESS
 ON THE PLANS. THE MINIMUM SIZE IS 20" X
 36" PER FBC 2309.6.
  
 5) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 5/8" EXPANSION BOLTS FOR THE OVERHEAD
 GARAGE DOOR BUCKS.
  
 6)THE GABLE END AT THE REAR AND ADJACENT
 TO THE VAULTED CEILING IS REQUIRED TO BE
 CONTINOUS FROM THE FLOOR TO THE CEILING
 DIAPHRAM PER FBC 1918.3.2. PLEASE
 PROVIDE A DETAIL OF THE RAKE BEAM AT
 THIS LOCATION.
  
 7) THE SITE SPECIFIC PRODUCT APPROVALS
 FOR THE NORANDEX PRODUCTS IS REQUIRED TO
 HAVE THE JOB SITE LOCATION ON THE FORM.
  
 8) THE SITE SPECIFIC PROD. APPROVALS FOR
 THE NORANDEX PRODUCTS DOES NOT INCLUDE
 A HORIZONTAL GLIDER WINDOW WITH A XOX
 CONFIGURATION AS IS SHOWN ON THE PLANS.
 PLEASE SUBMIT ONE FOR THIS WINDOW.
  
 9) THE R VALUES GIVEN FOR THE INSULATION
 AT THE EXTERIOR CONC. WALLS AND THE WOOD
 FRAME ADJACENT WALLS ON THE ENERGY
 CALCULATIONS ARE REVERSED. PLEASE
 CORRECT.
  
 10) PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS AND UL LISTING
 INFORMATION FOR THE ONE HOUR FIRE RATED
 GLASS BLOCK ASSEMBLY.
  
 11) INDICATE ON THE PLANS THE SIZE OF
 THE FIXED GLASS TRANSOM ABOVE THE FRONT
 DOOR.
  
 12) THE INSTALLATION SCHEDULE FOR THE
 STORM PANELS HAS THE WRONG SIZES FOR THE
 TRANSOM ABOVE THE FRONT DOOR, SIDELITE
 AT FRONT DOOR, THE BATHROOM AND MASTER
 BED ROOM WINDOWS. PLEASE CHECK THE PLANS
 AND REVISE.
  
 13) THE SURVEY HAS THE WRONG CASE # AND
 DATE FOR THE LOMR WITH THE FLOOD ZONE
 INFORMATION. PLEASE CORRECT.
  
 14) PLEASE INDICATE ON THE PLANS WHICH
 OPTIONS ARE BEING USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved