2003-02-06 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY ON PLANS THAT WIRE MESH IN
 SLAB IS TO BE SUPPORTED AS REQUIRED BY
 FBC 1909.3.
  
 3) THE WINDOW IN BATH #2 WHICH IS WITHIN
 THREE FEET HORIZONTALLY OF THE TUB/
 SHOWER IS REQUIRED TO HAVE SAFETY GLASS.
 THIS IS NOT CLEARLY INDICATED BY GENERAL
 NOTE #9 ON SHEET 1. PLEASE REVISE. SEE
 FBC 2405.2.1.
  
 4) SPECIFY THE SIZE OF THE ATTIC ACCESS
 ON THE PLANS. THE MINIMUM SIZE IS 20" X
 36" PER FBC 2309.6.
  
 5) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 5/8" EXPANSION BOLTS FOR THE GARAGE DOOR
 BUCKS ON SHEET 4.
  
 6) THE GABLE END AT THE REAR AND
 ADJACENT TO THE VAULTED CEILING IS
 REQUIRED TO BE CONTINOUS FROM THE FLOOR
 TO CEILING DIAPHRAGM PER FBC 1918.3.2.
 PLEASE PROVIDE A DETAIL OF THE RAKE
 BEAM IN THIS AREA.
  
 7) THE SITE SPECIFIC ENGINEERING FOR THE
 NORANDEX WINDOWS, DOORS AND MULLIONS ARE
 REQUIRED TO HAVE THE EMBOSSED SEAL OF
 THE ENGINEER/ARCHITECT FOR THE STRUCTURE
 AND THE LOCATION OF THE JOB ON THE FORM.
 THIS A REQUIREMENT OF THE BUILDING
 OFFICIAL PER CITY AMENDMENTS TO THE FBC
 103.7.
  
 8) THE R VALUES GIVEN FOR THE INSULATION
 AT THE CONCRETE EXTERIOR WALLS AND THE
 WOOD FRAME ADJACENT WALLS ON THE ENERGY
 CALCS. ARE REVERSED. PLEASE CORRECT.
  
 9) PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS AND UL LISTING
 INFORMATION FOR THE ONE HOUR FIRE RATED
 GLASS BLOCK ASSEMBLY.
  
 10) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS.
  
 11) PROVIDE PRODUCT APPROVALS FOR THE
 HORIZONTAL GLIDER WINDOW WITH THE XOX
 CONFIGURATION AS SHOWN ON THE PLANS. THE
 NORANDEX SUBMITTAL ONLY COVERS WINDOWS
 WITH AN XO CONFIGURATION.
  
 12) THE SURVEY HAS THE WRONG CASE # AND
 DATE FOR THE LOMR WITH THE FLOOD ZONE
 INFORMATION. PLEASE CORRECT.
  
 13) PLEASE CLARIFY ON PLANS IF OPTIONAL
 REAR PORCH IS BEING BUILT. CROSS OFF
 OPTIONS IF THEY ARE NOT TO BE USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202