2003-02-06 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SPECIFY ON PLANS THAT WIRE MESH IN |
| SLAB IS TO BE SUPPORTED AS REQUIRED BY |
| FBC 1909.3. |
| |
| 3) THE WINDOW IN BATH #2 WHICH IS WITHIN |
| THREE FEET HORIZONTALLY OF THE TUB/ |
| SHOWER IS REQUIRED TO HAVE SAFETY GLASS. |
| THIS IS NOT CLEARLY INDICATED BY GENERAL |
| NOTE #9 ON SHEET 1. PLEASE REVISE. SEE |
| FBC 2405.2.1. |
| |
| 4) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| ON THE PLANS. THE MINIMUM SIZE IS 20" X |
| 36" PER FBC 2309.6. |
| |
| 5) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| 5/8" EXPANSION BOLTS FOR THE GARAGE DOOR |
| BUCKS ON SHEET 4. |
| |
| 6) THE GABLE END AT THE REAR AND |
| ADJACENT TO THE VAULTED CEILING IS |
| REQUIRED TO BE CONTINOUS FROM THE FLOOR |
| TO CEILING DIAPHRAGM PER FBC 1918.3.2. |
| PLEASE PROVIDE A DETAIL OF THE RAKE |
| BEAM IN THIS AREA. |
| |
| 7) THE SITE SPECIFIC ENGINEERING FOR THE |
| NORANDEX WINDOWS, DOORS AND MULLIONS ARE |
| REQUIRED TO HAVE THE EMBOSSED SEAL OF |
| THE ENGINEER/ARCHITECT FOR THE STRUCTURE |
| AND THE LOCATION OF THE JOB ON THE FORM. |
| THIS A REQUIREMENT OF THE BUILDING |
| OFFICIAL PER CITY AMENDMENTS TO THE FBC |
| 103.7. |
| |
| 8) THE R VALUES GIVEN FOR THE INSULATION |
| AT THE CONCRETE EXTERIOR WALLS AND THE |
| WOOD FRAME ADJACENT WALLS ON THE ENERGY |
| CALCS. ARE REVERSED. PLEASE CORRECT. |
| |
| 9) PROVIDE THE MANUFACTURER'S |
| SPECIFICATIONS AND UL LISTING |
| INFORMATION FOR THE ONE HOUR FIRE RATED |
| GLASS BLOCK ASSEMBLY. |
| |
| 10) PROVIDE A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. |
| |
| 11) PROVIDE PRODUCT APPROVALS FOR THE |
| HORIZONTAL GLIDER WINDOW WITH THE XOX |
| CONFIGURATION AS SHOWN ON THE PLANS. THE |
| NORANDEX SUBMITTAL ONLY COVERS WINDOWS |
| WITH AN XO CONFIGURATION. |
| |
| 12) THE SURVEY HAS THE WRONG CASE # AND |
| DATE FOR THE LOMR WITH THE FLOOD ZONE |
| INFORMATION. PLEASE CORRECT. |
| |
| 13) PLEASE CLARIFY ON PLANS IF OPTIONAL |
| REAR PORCH IS BEING BUILT. CROSS OFF |
| OPTIONS IF THEY ARE NOT TO BE USED. |
| |