2003-01-27 00:00:00************ NOTE REDLINED *************
  
 1)NOTE: PLEASE SEE OCP AND WIRE SIZE
 SHOWN ON PANEL A FOR SUB-PANEL. ONE
 SHOWN AS 40A ON #10 AND RISER SHOWS AS
 #6 AND 60A OCP.
 PLEASE REVISE AND SUBMIT BEFORE ROUGH.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  