2003-03-21 00:00:00 | **********CORRECTIONS************ | | | | 1.)DRAWINGS ARE STILL MISSING | | INFORMATION REQUIRED BY SEC 1606.1.7 | | ITEM 4, FBC 2001. | | | | 2.)DESIGN PARAMETERS PAGE INDICATE THE | | BUILDING AS A PARTIALLY ENCLOSED | | BUILDING.PLEASE REVISE. | | | | 3.)COMPONENT AND CLADDING DESIGN | | WIND PRESSURES ON FIRST PAGE DO NOT | | MATCH ROOF COVERING CLADDING PRESSURES | | ON SHEET A-4.PLEASE CLARIFY. | | | | 3.)AS REQUESTED BY JULIO GOMEZ, | | PLEASE GIVE INFORMATION AS TO WHY | | BEDROOMS 1 & 2 HAVE SAFETY GLASS. | | | | 4.)PROVIDE A DETAIL FOR THE RAILING; | | MATERIAL, DIMENSIONS, ATTACHMENTS, AND | | LOAD INFORMATION (FBC 1608.2.2). | | | | 5.)ROOF PITCH ON PLANS IS 3.5/12. | | ROOF PITCH ON TRUSS DRAWINGS IS 4/12. | | PLEASE REVISE. | | | | 6.)PROVIDE PRODUCT APPROVALS FOR | | THE FRONT DOOR.THE PRODUCT APPROVAL | | SUBMITTED IS FOR A SOLID DOOR, NOT ONE | | WITH A WINDOW. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | 561-659-8096, EXTENSION 8340 |
|