2003-03-21 00:00:00**********CORRECTIONS************
  
 1.)DRAWINGS ARE STILL MISSING
 INFORMATION REQUIRED BY SEC 1606.1.7
 ITEM 4, FBC 2001.
  
 2.)DESIGN PARAMETERS PAGE INDICATE THE
 BUILDING AS A PARTIALLY ENCLOSED
 BUILDING.PLEASE REVISE.
  
 3.)COMPONENT AND CLADDING DESIGN
 WIND PRESSURES ON FIRST PAGE DO NOT
 MATCH ROOF COVERING CLADDING PRESSURES
 ON SHEET A-4.PLEASE CLARIFY.
  
 3.)AS REQUESTED BY JULIO GOMEZ,
 PLEASE GIVE INFORMATION AS TO WHY
 BEDROOMS 1 & 2 HAVE SAFETY GLASS.
  
 4.)PROVIDE A DETAIL FOR THE RAILING;
 MATERIAL, DIMENSIONS, ATTACHMENTS, AND
 LOAD INFORMATION (FBC 1608.2.2).
  
 5.)ROOF PITCH ON PLANS IS 3.5/12.
 ROOF PITCH ON TRUSS DRAWINGS IS 4/12.
 PLEASE REVISE.
  
 6.)PROVIDE PRODUCT APPROVALS FOR
 THE FRONT DOOR.THE PRODUCT APPROVAL
 SUBMITTED IS FOR A SOLID DOOR, NOT ONE
 WITH A WINDOW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-659-8096, EXTENSION 8340