2003-03-06 00:00:001-DRAWINGS ARE STILL MISSING INFORMATION
 REQUIRED BY SEC. 1606.1.7 FBC 2001.
 SEE THIS SECTION FOR REQUIRED FIVE (5)
 ITEMS TO BE INCLUDED IN DRAWINGS.
 2-CLARIFY WHAT ARE THE DESIGN WIND PRE-
 SSURES WRITTEN BY HAND ON THE SITE
 PLAN. ARE THESE FOR COMPONENT AND
 CLADDING?. PLEASE, REVISE ORIGINAL
 DRAWING. DON'T WRITE IT BY HAND.
 3-CLARIFY WHY WINDOWS ON BEDROOMS 1 & 2
 HAVE SAFETY GLASS?. SEC. 104.2.1.2
 CITY AMEMDMENTS TO FBC 2001.
 4-DIMENSIONS GIVEN ON SITE PLAN DON'T
 ADD UP CORRECTLY. REVISE AS REQUIRED.
 5-PROVIDE DETAIL/SPECS FOR CEILING INS-
 TALLATION AT FRONT AND REAR PORCH.
 CLEARLY SPECIFY FASTENERS AND SPACING
 AS REQ'D BY ASTM C926 AND ASTM C1063.
 SECTION 2504.2 FBC 2001.
 6-STORM SHUTTERS INFORMATION SUBMITTED:
 A)DRAWINGS DON'T MATCH PRODUCT APPROVAL.
  
 7-IMPACT FEES: NEED DRAWINGS STAMPED BY
 PALM BEACH COUNTY SHOWING EITHER NO
 FEES DUE OR CREDIT FOR EXISTING HOUSE.
 8-NEED PRODUCT APPROVAL FOR ENTRY DOOR
 W/ GLASS. SEE EXTERIOR ELEVATIONS.
 **NOTE: CLARIFY WHY ENTRY DOOR HAVE NOT
 STORM SHUTTERS IF IT HAS GLASS?SEE
 EXTERIOR ELEVATIONS.
 9-REVISE STRUCTURAL BUCK DETAIL. SEE
 SECTION 1707.4.4 FBC 2001 FOR SPECIFIC
 REQUIREMENTS FOR 2X BUCK AND REVISE
 DETAIL ACCORDINGLY. ALSO, DRAW DETAIL
 AT A LARGER SCALE TO BE ABLE TO SEE
 BUCK LOCATION.