2003-03-06 00:00:00 | 1-DRAWINGS ARE STILL MISSING INFORMATION |
| REQUIRED BY SEC. 1606.1.7 FBC 2001. |
| SEE THIS SECTION FOR REQUIRED FIVE (5) |
| ITEMS TO BE INCLUDED IN DRAWINGS. |
| 2-CLARIFY WHAT ARE THE DESIGN WIND PRE- |
| SSURES WRITTEN BY HAND ON THE SITE |
| PLAN. ARE THESE FOR COMPONENT AND |
| CLADDING?. PLEASE, REVISE ORIGINAL |
| DRAWING. DON'T WRITE IT BY HAND. |
| 3-CLARIFY WHY WINDOWS ON BEDROOMS 1 & 2 |
| HAVE SAFETY GLASS?. SEC. 104.2.1.2 |
| CITY AMEMDMENTS TO FBC 2001. |
| 4-DIMENSIONS GIVEN ON SITE PLAN DON'T |
| ADD UP CORRECTLY. REVISE AS REQUIRED. |
| 5-PROVIDE DETAIL/SPECS FOR CEILING INS- |
| TALLATION AT FRONT AND REAR PORCH. |
| CLEARLY SPECIFY FASTENERS AND SPACING |
| AS REQ'D BY ASTM C926 AND ASTM C1063. |
| SECTION 2504.2 FBC 2001. |
| 6-STORM SHUTTERS INFORMATION SUBMITTED: |
| A)DRAWINGS DON'T MATCH PRODUCT APPROVAL. |
| |
| 7-IMPACT FEES: NEED DRAWINGS STAMPED BY |
| PALM BEACH COUNTY SHOWING EITHER NO |
| FEES DUE OR CREDIT FOR EXISTING HOUSE. |
| 8-NEED PRODUCT APPROVAL FOR ENTRY DOOR |
| W/ GLASS. SEE EXTERIOR ELEVATIONS. |
| **NOTE: CLARIFY WHY ENTRY DOOR HAVE NOT |
| STORM SHUTTERS IF IT HAS GLASS?SEE |
| EXTERIOR ELEVATIONS. |
| 9-REVISE STRUCTURAL BUCK DETAIL. SEE |
| SECTION 1707.4.4 FBC 2001 FOR SPECIFIC |
| REQUIREMENTS FOR 2X BUCK AND REVISE |
| DETAIL ACCORDINGLY. ALSO, DRAW DETAIL |
| AT A LARGER SCALE TO BE ABLE TO SEE |
| BUCK LOCATION. |